Datacenter “G50” is conveniently located close to the heart of capital of Ukraine, Kyiv, on the Gaidar street in the same building with the technical platforms of Internet traffic exchanges (UA-IX, DTEL-IX, GIGANET), within a reach of all local and foreign telecommunication carriers.

We provide pure-play and co-location hosting services with a highly flexible, secure and scalable IT and hosting environment fully compliant with TIER ANSI/TIA-942 standards and have 2N+1 redundancy for power supplies and cooling systems and N+1 for all other environment systems.

Our Services

Colocation

Placement of the server equipment of the subscriber on the technical stand of the Data Center.
Connecting it to uninterrupted power supply and unlimited Internet channel

Our Data Center

Time Hours

Design, Photography

Time Hours

Design, Photography

Time Hours

Design, Photography

Time Hours

Design, Photography

Time Hours

Design, Photography

Time Hours

Design, Photography

Time Hours

Design, Photography

Time Hours

Design, Photography

Infrastructure

Equipment placement

  • Standard cabinet units 49 600 x 1000-1200 mm;
  • Air supply – from the bottom in front (60-80% perforation) into the cold corridor;
  • 2 independent power rays in each cabinet;
  • Payment for consumed electricity – according to the individual meter. You pay only for that amount of electricity which you actually use;
  • Ability to accommodate non-standard cabinets by an individual project;
  • Minimum rent amount - 5 units;
  • Raised floor with an antistatic coating, increasing in the load zones and with an additional shielding, reinforced by metal sheet in the bottom;
  • System of screening and removing of static capacity in the air stream under the raised floor;
  • Place to work with the equipment, if there is a necessity for its enduring adjustment or disassembling.

Power supply

  • Total capacity of 2 MVA;
  • Independent input power of 2 x 1 MVA;
  • Two independent transformers and two distributive groups TS;
  • Two separate 10 kV lines that are connected to two independent transformers 27 / 10kV;
  • Automatic Gen Set;
  • Fuel capacity for 24 hours;
  • UPS by Emersion production of APM type, modular system redundancy 2N + 1;
  • Minimum 12-minute work from UPS battery at a full load;
  • Automatic bypass of UPS;
  • Intelligent system of remote monitoring and equipment control Liebert IntelliSlot;
  • Automatic Transfer Switch (ATS);
  • ATS with electromechanical blocking and switching on static actuators – absence of sticking contacts and scorching contactors probability and protection from humans’ errors;
  • Power distributors of low voltage with independent protection of each ray and hand-held bypass, with the ability to switch two supply lines;
  • Independent from grounding TS system of working and protective grounding - 2 spaced drillholes with the depths of 68 and 76 meters combined by cooper bus-bar;
  • Spatial separation of power cables and low-voltage networks;
  • Engineering arranging of the perimeter substation additional security.

Cooling

  • Precision-build Emerson Liebert HPM dry conditioners with electronically adjustable performance and redundancy N + 1;
  • Intelligent remote centralized monitoring and equipment controlling system Liebert Intellislot;
  • Absence of circulating water under pressure in the server room;
  • Minimal risk of flooding.

Firefighting

  • System of gas volumetric firefighting;
  • Equally distributed placement of balloons in the room and under the raised floor;
  • Absence of gas lines, distributors and other elements that reduce the reliability of gas operation and its supply to the quenching;
  • Highly sensitive system of VESDA for the early smoke detection;
  • Fire-resistance of shielding constructions - at least 2 hours;
  • SC is made from the combustible cable;
  • Fireproof doors for all entrances.

Connecting

  • Full range of telecommunications services on preferential terms;
  • Free choice of any provider;
  • Connecting by optical (Single Mode) or copper (Cat 6) interfaces;
  • Independent spaced bushings into the building;
  • Individual cross room for connection with service providers;
  • Ready-optic backbone for connection on sites Gaidar, 50 and Leontovycha 9;
  • Ability to connect E1 (G.703);
  • Lease of channels and streams in Kyiv and Ukraine.

Security

  • Physical security provided by leading security companies;
  • Centralized security management system;
  • Possibility of remote monitoring of leased cabinets (for equipment);
  • Full review of all areas and approaches to them, cabinets, hot and cold corridors of the territory adjoined to the building territory by digital video surveillance CCTV (2 independent systems);
  • Keeping records from all cameras for 10 days;
  • Withdrawal images on security personnel’s monitors and to general management center G50;
  • Monitoring of protected space motion sensors;
  • Metal certified fireproof doors of intensive type;
  • Blocking of all doors with electric locks with a pullout force of more than 300 kg.
  • Registration system and access control with using of contactless readers.
  • Three turn access control to premises of server data centers;
  • Entrance into server-sides through gateways with the line of access control and video-monitoring;
  • Lighting perimeter of the building and protected area;
  • Engineering structures of physical area protection.